6.2
2340, Short circuit (motor-side)
The drive hardware detected an over-current on the motor phases. The short circuit detection was triggered.
Diagnostic Code (Hex.)
2340
Class
Error
Standard Reaction
Torque off
Possible Causes
Short circuit in the motor cable.
Short circuit in the motor winding.
Internal: 0x2340, Short circuit (motor-side)
Multi axis servo system - AX8000
Diagnostic Code (Dez.)
9024
Type
Overcurrent error
Reset
A fatal error occurred. A device reboot is required.
Solutions
Check the motor cable
Check the motor winding with an high voltage test or
check the winding resistance.
Version: 1.1
Diagmessages of module AxisMain