6395, Factor Group Parameters: Position Encoder Resolution Illegal Motor Revolutions - Beckhoff AX8000 User Information

Multi axis servo system diagnostic messages
Hide thumbs Also See for AX8000:
Table of Contents

Advertisement

6.28
6395, Factor Group Parameters: Position encoder
resolution illegal motor revolutions
The actual combination of the factor group Parameters is not allowed for this Device.
Diagnostic Code (Hex.)
6395
Class
Error
Standard Reaction
Axis is inoperable
Possible Causes
The position encoder resolution - motor revolutions
contains an illegal value (Object 0x608F/2 ChA or
0x688F/2 ChB).
Internal: 0x6395, Factor Group Parameters: Position encoder resolution illegal motor revolutions
Multi axis servo system - AX8000
Diagnostic Code (Dez.)
25493
Type
Error
Reset
Execute Reset-Command (Fault reset).
Solutions
Please compare it to your encoder values.
Version: 1.1
Diagmessages of module AxisMain