3-2.4 Status Indicating Leds - Kidde ARIES Installation, Operation And Maintenance Manual

Fire alarm/suppression
Table of Contents

Advertisement

3-2.4
Status Indicating LEDs
Table 3-3 lists the names and functions of the system status LEDs on the display.
LED
COLOR
Power On
Green
Alarm
Red
Pre-Alarm
Yellow
Trouble
Yellow
Supervisory
Yellow
Silence
Yellow
August 2013
Table 3-3. System Status LEDs and Functions
A steady LED indicates primary AC power is on at acceptable levels.
An unlit LED indicates unacceptable AC power levels or AC power is
disconnected.
A flashing LED indicates one or more unacknowledged alarm events, or that a
previously-acknowledged non-latching alarm device has issued an alarm-off
report.
A steady LED indicates all alarm events and alarm-off reports have been
acknowledged.
The LED turns off when the control unit is reset if all current alarm events and
alarm-off messages have been acknowledged and none of the alarm-initiating
devices are reporting alarms.
A flashing LED indicates unacknowledged pre-alarm events.
A steady LED indicates all current pre-alarm events have been acknowledged.
The LED turns off when the control unit receives pre-alarm-off messages from
all alarm-initiating devices that had reported a pre-alarm.
A flashing LED indicates unacknowledged trouble events.
A steady LED indicates all trouble events have been acknowledged.
The LED turns off when the control unit receives trouble-off messages from all
SLC or IIM devices or control-unit monitoring circuitry that had reported
trouble conditions.
A flashing LED indicates one or more unacknowledged supervisory events.
A steady LED indicates all supervisory events have been acknowledged.
The LED turns off when the control unit receives supervisory-off messages
from all initiating devices that had reported supervisory conditions.
A steady LED indicates the Silence Key has been pressed after all current
alarm events have been acknowledged.
The LED turns off when 1) the control unit is reset, or 2) the Silence key is
pressed to toggle on any previously-silenced NACs and SLC-based modules.
The Silence key will repeatedly toggle the NACs and SLC-based modules off
and on and the Silence LED will track the activation state of the NACs and
modules until the control unit is reset.
3-4
FUNCTION
P/N 06-236530-001