Kidde ARIES Installation, Operation And Maintenance Manual page 169

Fire alarm/suppression
Table of Contents

Advertisement

Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 4 Key
4
Press "Scroll" Key
5
Press 6 Key
6
Use keypad to enter initiating device to report
"alarm off."
Press "Enter" Key to confirm selection.
7
Press 0 Key and Press "Enter" Key
8
Press "Acknowledge" Key
9
Repeat Steps 6 to 8 (as required)
10
Press "Backspace" Key (as required)
11
Press "Reset" Switch
P/N 06-236530-001
Action
3-87
Result
Initiate menu access
Gain access to menus
Enter Test-Menu branch
Access additional options
Select "Alarm Simulation Test"
Specify device to issue "alarm-off" message
Initiate "alarm-off" message
Make Alarm LED flash steadily
Report "alarm-off" for all simulated initiating
devices
Exit Menu System
Return to Normal Operating Condition
August 2013