3-2.5.2.4.14 How to Manually Register SLC Devices
SLC Device
Ionization Detectors
Photoelectric Detectors
Heat Detectors
Monitor Modules (AIs)
Monitor Modules (PALMs)
Monitor Modules (AAMs)
Relay Modules (AOs)
Control Modules (ASMs)
Remote Release Modules
(RRMs)
August 2013
Purpose: The ARIES Control Unit needs to know which SLC addresses
(of the 255 possible addresses) will be occupied by a SmartOne
detector, monitor module, relay module or control module. The
Registration Procedure enters an occupied address into the control-
unit's configuration memory for each SLC device that it encounters
during execution. The SLC devices must be uniquely addressed prior to
execution of the Registration Procedure.
The SLC devices are assigned the following default-operating
parameters:
0.8% per foot Pre-alarm Threshold
1.0% per foot Alarm Threshold
Latching Operation
Activates General-Alarm List
1.5% per foot Pre-alarm Threshold
2.0% per foot Alarm Threshold
Latching Operation
Activates General-Alarm List
120°F Pre-Alarm Threshold
135°F Alarm Threshold
Latching Operation
Activates General-Alarm List
ITLCO/CTLCO Off
Alarm-Initiating Device
Latching Operation
Activates General-Alarm List
Alarm-Initiating Device
Latching Operation
Activates General-Alarm List
Alarm-Initiating Device
Latching Operation
Activates General-Alarm List
Non-Silenceable Operation
In General-Alarm List
Non-Silenceable Operation
Enabled for Drill Activation
Activates in Walk Test
Solenoid, On Until Reset
The activation of any initiating device will activate the outputs in the
general-alarm list.
Note: SLC devices are also automatically registered and configured for
operation by the AutoLearn or AutoSetup Routines, or by a
configuration upload via the ARIES Configuration Program.
Exception: PALMS require additional configuration via the OCS
Program, and AAMs require additional configuration via the SET
Menu or the ACT Configuration Program after an AutoLearn
Procedure. Refer to Paragraph 3-2.5.2.4.12 to configure AAMs
via the SET Menu.
Default Operating Parameters
3-44