FACTORY MUTUAL REQUIREMENTS FOR PRE-ACTION
AND DELUGE SPRINKLER SYSTEMS
ARIES™ Fire Alarm/Suppression Control Unit applications that require Factory Mutual (FM)
Approval of pre-action and deluge sprinkler systems must conform to the following guidelines:
SmartOne® Thermal Detectors, Model THD-7252, must be installed at 20 ft. spacings. The
pre-alarm and alarm setpoint ranges are as follows:
Pre-Alarm: 80° to 155° F
Alarm: 135° to 155° F
The signaling line circuit must be configured for Style 6 wiring. Refer to Figure 2-14.
Provide 90 hours of standby battery and 10 minutes of alarm operation. Refer to Appendix
A.
Each release circuit is required to be configured for solenoid activation. The solenoid output
on-time period should be set to either "90 seconds" or "on until reset".
P/N 06-236530-001
Factory Mutual Requirements for Pre-Action
APPENDIX G
G-1
August 2013