Pre-Alarm State - Kidde ARIES Installation, Operation And Maintenance Manual

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.7
August 2013

PRE-ALARM STATE

The Pre-Alarm State occurs when a SmartOne automatic initiating device (such
as a smoke detector) senses a fire signature that is below its configured alarm-
threshold value but above a lower-threshold value called the "pre-alarm"
threshold. The ARIES can also enter the Pre-Alarm State if it receives a Pre-Alarm
Level-1 or -2 signal reported by a high-sensitivity smoke detector (HSSD)
communicating through the Intelligent Interface Module (IIM).
The upper line of the LCD display shows the pre-alarm event by the device
address, the change of state, and the device type. The lower line indicates the up-
to-40-character message assigned to the alarm device using the ARIES
configuration program.
Device Address 200
200 PREALARM
GROUND-FLOOR CONTROL ROOM
Device-Specific
Custom Message
Figure 3-23. Typical Pre-Alarm-Message Display
The following actions also occur when any pre-alarm condition is reported:
The Pre-Alarm LED flashes
The internal buzzer pulses
The pre-alarm event is stored in the event log
The pre-alarm message is transmitted to peripheral devices such as RDCMs
and ATM-Ls, if applicable
The pre-alarm message is communicated via the RS-232 ports
Point- or group-specific and general pre-alarm outputs will activate,
including previously-silenced outputs.
Pre-Alarm-On Indication
Device Type
PHOTOELECTRIC
3-108
P/N 06-236530-001