3-2.5.7
August 2013
PRE-ALARM STATE
The Pre-Alarm State occurs when a SmartOne automatic initiating device (such
as a smoke detector) senses a fire signature that is below its configured alarm-
threshold value but above a lower-threshold value called the "pre-alarm"
threshold. The ARIES can also enter the Pre-Alarm State if it receives a Pre-Alarm
Level-1 or -2 signal reported by a high-sensitivity smoke detector (HSSD)
communicating through the Intelligent Interface Module (IIM).
The upper line of the LCD display shows the pre-alarm event by the device
address, the change of state, and the device type. The lower line indicates the up-
to-40-character message assigned to the alarm device using the ARIES
configuration program.
Device Address 200
200 PREALARM
GROUND-FLOOR CONTROL ROOM
Device-Specific
Custom Message
Figure 3-23. Typical Pre-Alarm-Message Display
The following actions also occur when any pre-alarm condition is reported:
•
The Pre-Alarm LED flashes
•
The internal buzzer pulses
•
The pre-alarm event is stored in the event log
•
The pre-alarm message is transmitted to peripheral devices such as RDCMs
and ATM-Ls, if applicable
•
The pre-alarm message is communicated via the RS-232 ports
•
Point- or group-specific and general pre-alarm outputs will activate,
including previously-silenced outputs.
Pre-Alarm-On Indication
Device Type
PHOTOELECTRIC
3-108
P/N 06-236530-001