3-2.5.2.4.64 How to Register High-Sensitivity Smoke Detectors (HSSDs)
This Registration Procedure shall not be used to configure the HSSDs. This is
primarily a procedure to store these detectors in the ARIES's configuration
memory. The HSSDs shall be configured with the LaserNET Configuration
CAUTION
Program.
Step
1
Press 0 Key
2
Enter Password
3
Select the local node then press "Enter" or a
select a remote node number, press "Enter" then
enter the remote node's password.
4
Press 3 Key
5
Press "Scroll" Key twice
6
Press 8 Key
7
Press 3 Key
8
Use keypad to enter single HSSD or range of
HSSDs to register.
Press "Enter" Key to confirm selection.
9
Press "Backspace" Key (as required)
10
Wait until "Initializing Configuration" message
disappears from the display.
P/N 06-236530-001
Purpose: To inform the ARIES Control Unit of the quantity and
addresses of the HSSDs that will be connected to the IIM.
Note: The HSSDs are also automatically registered when included
with the IIM in a configuration upload via the ARIES
Configuration Program.
Action
3-79
Result
Initiate menu access
Gain access to menus
Access applicable control unit (if networked
system)
Enter Set-Menu branch
Access additional options
Select "HSDs" option
Select register HSDs
Specify single HSSD or range of HSSDs to be
registered
Exit Menu System
Initialization complete