3-2.5.2.5.20 How to Find a Duplicate Address
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 4 Key
4
Press "Scroll" Key twice
5
Press 9 Key
6
Press 1 Key
7
Enter duplicate SLC address when message "SLC
DOUBLE ADDRESS LED SELECTION UTILITY" is
displayed.
Use XXX format for address.
Press "Enter" Key to confirm duplicate address.
The lower line of the display changes to "PRESS
BACKSPACE TO EXIT"
8
Press "Backspace" Key at the prompt "PRESS
BACKSPACE TO EXIT".
9
Press "Backspace" Key (as required)
3-2.5.2.6
August 2013
Purpose: To clear the trouble message that appears when two SLC
devices have been accidentally assigned the same address. The
location of the affected SLC devices can be found by instructing the
control unit to modify the doubly addressed devices LED pulse pattern.
Note: Only one address can be selected at a time if more than one
double-address trouble exists.
Action
System Passwords
Password entry is required for all menu operations.
The ARIES System provides two distinct levels of program protection, as
required by UL Standard 864. The user can only access the menu system
by entering a valid password. Typical valid passwords consist of six digits,
but may be up to eight characters in length.
There are two security levels:
Level One, reserved for the system owner. This is the lowest-level
security.
Level Two, reserved for the system installer. This is medium-level
security.
Passwords can consist of up to eight numeric characters (0 - 9) which
allows access from the display. Alphanumeric characters can only be used
with the ACT program; however, if used, they will lock out any possible
entry to the menus from the display. Refer to the ARIES Programming
Guide for the procedure to create alphanumeric passwords. Table 3-5
describes the different password levels and their functions.
3-96
Result
Initiate menu access
Gain access to menus
Enter Test-Menu branch
Access additional "Test-Menu" options
Select "More Options"
Select "Find Dup Address" option
Specify duplicate address and initiate double-
address LED-selection utility.
The devices with the duplicate address will flash
their LEDs twice every 2 to 3 seconds. Locate the
devices and correct the addressing problem.
The control unit will continuously execute the
double-address LED-selection utility until
manually cancelled by a press of the "Backspace"
Key.
End double-address LED-selection utility after the
devices with duplicate addresses have been
located and addresses corrected.