Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 4 Key
4
Press "Scroll" Key
5
Press 6 Key
6
Press 1 Key to select SLC Alarm Simulation or
Press 2 Key to select HSD Alarm Simulation
7
Enter the SLC or HSD Address of the device to
test. Use XXX format for address.
Press "Enter" Key to confirm address selection.
8
Press 1 Key and Press "Enter" Key
9
Press "Acknowledge" and "Silence" Keys (as
appropriate)
10
Repeat Steps 7 to 9 (as required)
11
De-activate all simulated initiating devices
12
Press "Backspace" Key (as required)
3-2.5.2.5.9
Isolate all releasing outputs using the Isolate function and physically disconnect the
wiring to all agent-release, pre-action-sprinkler and auxiliary control circuits before
running any alarm-simulation test(s). Restore the system to normal operating
CAUTION
condition at the conclusion of these tests and any other functional tests that were
performed.
August 2013
Action
How to De-Activate an Alarm-Simulation Test
Purpose: To report an "alarm-off" message from an initiating device
whose activation was simulated.
Note: Each simulated alarm report must be manually de-activated
via this menu operation before the system can be returned
to normal operating condition.
3-86
Result
Initiate menu access
Gain access to menus
Enter Test-Menu branch
Access additional options
Select "Alarm Sim Test"
Specify device type to be alarm simulated
Specify the address of the device being tested
Initiate simulation
Execute proper operator procedures
Simulate multiple-device actuations
See Paragraph 3-2.5.2.5.9
Exit Menu System
P/N 06-236530-001