Kidde ARIES Installation, Operation And Maintenance Manual page 269

Fire alarm/suppression
Table of Contents

Advertisement

10 OHM LIMITING
RESISTOR
INITIATOR
Figure C-2. Agent Release Circuit Wiring - Initiators, Non-Power-Limited
Note: 1. Polarities must be observed.
2. Must be close nippled to Solenoid enclosures.
3. The ARC is Non-Power-Limited when in-line device not used.
4. Route Non-Powered-Limited wiring at least 1/4-inch away from all Power-Limited
wiring. Do not attach Power-Limited wiring to the same terminal block.
5. When using initiators, different types of initiators must NOT be mixed on the same
circuit. The limiting resistor is used to make the total circuit resistance equal to ±
1 ohm. The resistor must have a rating of 1 watt minimum.
6. Control Head P/Ns 90-487100-001, 87-120099-001, and 87-120099-002 when used
with the panel must include Solenoid P/N 83-100034-001 and Microswitch P/N 87-
120039-001.
C-4
UL LISTED AND FM APPROVED ASSEMBLY
The following actuator assembly is UL Listed and FM Approved.
Part Number
83-131025-001
P/N 06-236530-001
MAXIMUM WIRE RESISTANCE: 3 OHMS
Table C-4. UL Listed and FM Approved Actuator Assembly
Max. No. per Release Ckt.
Listed and Approved Releasing Devices
TB14 OR TB15
R1+
R2+
R1- R2-
MAXIMUM CURRENT UNDER
FAULT CONDITIONS: 5A
1
C-3
Max. Rel. Ckt. Resistance
3 ohms
August 2013