Kidde ARIES Installation, Operation And Maintenance Manual page 123

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.4.11 How to Change a Thermal Detector's Pre-Alarm and Alarm Thresholds
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 3 Key
4
Press 3 Key
5
Press 2 Key
6
Press 3 Key
7
Use keypad to enter single detector or range of
detectors to change pre-alarm/alarm thresholds.
Press "Enter" Key to confirm selection.
8
Press 1 Key for 50-ft. Spacing or
Press 2 Key for 70-ft. Spacing.
Press "Enter" Key to confirm selection.
9
Use keypad to enter pre-alarm threshold.
Press "Enter" Key to confirm selection.
10
Use keypad to enter alarm threshold.
Press "Enter" Key to confirm selection.
11
Wait until "Updated Thresholds for Device x"
message disappears from the display.
12
Press "Backspace" Key (as required)
P/N 06-236530-001
Purpose: To change the pre-alarm and alarm thresholds of one or more
thermal detectors. The thermal detector is UL Listed and FM Approved
for alarm reporting anywhere in the range of 135° F to 155°F when
used with a 50-foot spacing, or anywhere in the range of 135°F to
145°F when used with a 70-foot spacing. Alarm thresholds can be set
in 1F° increments. A pre-alarm threshold can also be set anywhere
within the temperature range of 80°F to 135°F, but must be less than
the detector's alarm threshold.
The alarm ranges for the thermal detectors are summarized below:
Spacing (ft.)
50
70
Action
3-41
Pre-Alarm Range
(°F)
80 - 135
80 - 135
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access "SLC Devices" option
Select "Configuration"
Select Thermal Detectors
Specify detectors to change
Specify detector application
Set pre-alarm threshold
Set alarm threshold
Exit Menu System
Alarm Range (°F)
135 - 155
135 - 145
August 2013