3-2.5.2.5.18 How to Run a Lamp Test
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 4 Key
4
Press "Scroll" Key Twice
5
Press 4 Key
6
Press "Backspace" Key (as required)
3-2.5.2.5.19 How to Measure SLC Resistance
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 4 Key
4
Press "Scroll" Key Twice
5
Press 8 Key
6
Press "Backspace" Key (as required)
P/N 06-236530-001
Purpose: To test the LEDs on the keypad/display.
Action
Purpose: To measure the SLC line resistance.
Note: The SLC line resistance cannot be measured for Class-B SLCs
with T-Tapping.
Action
3-95
Result
Initiate menu access
Gain access to menus
Enter Test-Menu branch
Access additional "Test-Menu" options
Run LED test. Confirm that all LEDs illuminate.
Exit Menu System
Result
Initiate menu access
Gain access to menus
Enter Test-Menu branch
Access additional "Test-Menu" options
Select "SLC Resistance" option.
Record resistance reading that appears in the
display. Resistance cannot exceed 40 ohms.
Exit Menu System