Error Message
HSDAddr Auto Offset Trouble On
HSDAddr Detector Trouble On
HSDAddr High AirFlow On
HSDAddr Low AirFlow On
HSDAddr
Missing On
P/N 06-236530-001
Table 5-4. IIM Events
Probable Cause
The HSSD at address Addr is
reporting an offset problem. This is
probably a problem with the
background obscur-ation level in the
area of the HSSD.
A fault in the HSSD with IIM address
Addr
A problem in the HSSD with IIM
address Addr. Excessively high air
flow through the piping system
A problem in the HSSD with IIM
address Addr. Low air flow through
the piping system
Loss of communications to HSSD at
IIM address Addr
5-15
Corrective Action
•Work with the end user to improve
the air quality in the HSSD location.
•Check the IIM-to-HSSD wiring
connections
•Use LaserNET to troubleshoot the
HSSD
•Refer to ORION-XT Installation,
Operation, and Maintenance Manual,
P/N 89.200.
•Use LaserNET to troubleshoot the
HSSD
•Refer to ORION-XT Installation,
Operation, and Maintenance Manual,
P/N 89.200.
•Look for leaks in the HSSD's piping
system
•Use LaserNET to troubleshoot the
HSSD. The airflow may need to be
re-normalized.
•Refer to ORION-XT Installation,
Operation, and Maintenance Manual,
P/N 89.200.
•Look for blockages in the HSSD's
piping system
•Use LaserNET to troubleshoot the
HSSD. The airflow may need to be
re-normalized.
•Refer to ORION-XT Installation,
Operation, and Maintenance Manual,
P/N 89.200.
•Check the IIM-to-HSSD wiring
connections
•Ensure that HSSD has not been
removed
•Use the procedure in
Section 3-2.5.2.4.15 to de-register
the address if no HSSD should
occupy that address.
•Check IIM wiring for excessive
capacitance and/or resistance.
•Use LaserNET to troubleshoot the
HSSD.
•Refer to ORION-XT Installation,
Operation, and Maintenance Manual,
P/N 89.200.