Kidde ARIES Installation, Operation And Maintenance Manual page 124

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.4.12 How to Change the Configuration of an Addressable AlarmLine Module
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 3 Key
4
Press 3 Key
5
Press 2 Key
6
Press 4 Key
7
Use keypad to enter single module or range of
modules to change configuration settings.
Press "Enter" Key to confirm selection.
8
Use keypad to enter variable-alarm-threshold
switch setting.
Press "Enter" Key to confirm selection.
9
Press 1 Key to enable pre-alarm reporting or
Press 2 Key to disable pre-alarm reporting.
Press "Enter" Key to confirm selection.
10
Press 1 Key to enable alarm reporting or
Press 2 Key to select overheat reporting.
Press "Enter" Key to confirm selection.
11
Wait until "Updated Thresholds for Device x"
message disappears from the display.
12
Press "Backspace" Key (as required)
August 2013
Purpose: To change one or more of the following Addressable
AlarmLine Module (AAM) operating characteristics for a single module
or range of modules: pre-alarm and alarm thresholds as defined by the
module's variable-threshold-setting switch; pre-alarm reporting;
alarm or overheat reporting
Note: The AAM will create an "Overheat" message on the display if its
alarm threshold is exceeded and it is configured for overheat
reporting. The control unit buzzer will also activate.
Action
3-42
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access "SLC Devices" option
Select "Configuration"
Select AlarmLine
Specify modules to change
Specify pre-alarm/alarm thresholds based upon
footage and ambient conditions.
Enable/Disable pre-alarm reporting
Select type-of-event reporting
Exit Menu System
P/N 06-236530-001