Kidde ARIES Installation, Operation And Maintenance Manual page 236

Fire alarm/suppression
Table of Contents

Advertisement

Control-Unit-Based-Output Events
Error Message
AR1 Open Circuit Trouble On
AR1 Short Circuit Trouble On
AR2 Open Circuit Trouble On
AR2 Short Circuit Trouble On
AR3 Open Circuit Trouble On
AR3 Short Circuit Trouble On
AR4 Open Circuit Trouble On
AR4 Short Circuit Trouble On
SG1 Open Circuit Trouble On
SG1 Short Circuit Trouble On
SG2 Open Circuit Trouble On
SG2 Short Circuit Trouble On
SG3 Open Circuit Trouble On
August 2013
Table 5-2. Control-Unit-Based-Output Events
Probable Cause
Open circuit in field wiring connected
to main circuit board TB12
Short circuit in field wiring connected
to main circuit board TB12
Open circuit in field wiring connected
to main circuit board TB11
Short circuit in field wiring connected
to main circuit board TB11
Open circuit in field wiring connected
to main circuit board TB7. Combo-1
Circuit is configured as a release
circuit.
Short circuit in field wiring connected
to main circuit board TB7. Combo-1
Circuit is configured as a release
circuit.
Open circuit in field wiring connected
to main circuit board TB6. Combo-2
Circuit is configured as a release
circuit.
Short circuit in field wiring connected
to main circuit board TB6. Combo-2
Circuit is configured as a release
circuit.
Open circuit in field wiring connected
to main circuit board TB5
Short circuit in field wiring connected
to main circuit board TB5
Open circuit in field wiring connected
to main circuit board TB14
Open circuit in field wiring connected
to main circuit board TB14
Open circuit in field wiring connected
to main circuit board TB7. Combo-1
Circuit is configured as a NAC.
5-6
Corrective Action
• Look for discontinuity in Release-1
field wiring. Refer to
Paragraph 2-11.
• Troubleshoot Release-1 wiring by
breaking-up circuit to isolate short
circuit to specific leg.
• Look for discontinuity in Release-2
field wiring. Refer to
Paragraph 2-11.
• Troubleshoot Release-2 wiring by
breaking-up circuit to isolate short
circuit to specific leg.
• Look for discontinuity in Combo-1
field wiring. Refer to
Paragraph 2-10.2.
• Troubleshoot Combo-1 wiring by
breaking-up circuit to isolate short
circuit to specific leg.
• Look for discontinuity in Combo-2
field wiring. Refer to
Paragraph 2-10.2.
• Troubleshoot Combo-2 wiring by
breaking-up circuit to isolate short
circuit to specific leg.
• Check for missing 10k end-of-line
resistor.
• Look for discontinuity in NAC1 field
wiring.
• Troubleshoot NAC1 wiring by
breaking-up circuit to isolate short
circuit to specific leg.
• Check for missing 10k end-of-line
resistor.
• Look for discontinuity in NAC2 field
wiring.
• Troubleshoot NAC2 wiring by
breaking-up circuit to isolate short
circuit to specific leg.
• Check for missing 10k end-of-line
resistor.
• Look for discontinuity in Combo-1
field wiring.
P/N 06-236530-001