2-11.2
Releasing Circuits for Single Control Head or Solenoid Valve
Each releasing circuit can be configured to activate either one Kidde control head or one
pre-action-sprinkler or deluge-sprinkler valve. Total current output of the ARIES power
supply must not exceed 5.4 A. Figure 2-24 shows a releasing circuit wired for single-
control-head or single-solenoid-valve actuation.
TB12 or
TB11
A releasing circuit is supervised and power limited when the in-line device, P/N
06-220023-001, is wired in series with the single control head or solenoid valve. See
Appendix C for compatible control heads and solenoid valves. Refer to the ARIES
Programmer's Guide to configure the releasing circuits for single-control-head or single-
solenoid-valve actuation.
Route non-power-limited wiring at least 1/4 inch away from all power-limited wiring.
P/N 06-236530-001
Figure 2-23. Releasing-Circuit Wiring for Actuator
Release 1 or
Release 2
1
2
3
4
Supervised and Power-Limited
In-Line Releasing Device (P/N 06-220023-001)
(Must be close nippled to solenoid enclosure)
Figure 2-24. Releasing-Circuit Wiring for Single Solenoid
Solenoid
(Refer to Appendix C)
Red
Blk
2-23
August 2013