Kidde ARIES Installation, Operation And Maintenance Manual page 159

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.4.62 How to Register an Intelligent Interface Module (IIM)
The IIM Registration Procedure shall not be used to configure the HSSDs
connected to the IIM. This is primarily a procedure to store the IIM in the
ARIES's configuration memory. The HSSDs connected to the IIM shall be
CAUTION
configured with the LaserNET Configuration Program.
Step
1
Press 0 Key
2
Enter Password
3
Select the local node then press "Enter" or a
select a remote node number, press "Enter" then
enter the remote node's password.
4
Press 3 Key
5
Press "Scroll" Key twice
6
Press 8 Key
7
Press 1 or 2 Key to select the port the IIM is
connected to and then press "Enter"
8
Press "Backspace" Key (as required)
9
Wait until "Initializing Configuration" message
disappears from the display.
P/N 06-236530-001
Purpose: To inform the ARIES Control Unit that it will be configured
with an Intelligent Interface Module. The IIM must be registered in the
control unit's configuration memory to work correctly.
Note: The IIM is also automatically registered when included in a
configuration upload via the ARIES Configuration Program.
Action
3-77
Result
Initiate menu access
Gain access to menus
Access applicable control unit (if networked
system)
Enter Set-Menu branch
Access additional options
Select "HSDs" option
Select "RS232A" or "RS232B"
Assign port to IIM
Exit Menu System
Initialization complete
August 2013