Kidde ARIES Installation, Operation And Maintenance Manual page 176

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.5.17 How to De-Activate Remote Release Modules
There is no indication at the control unit that an output is activated. Be sure to
de-activate the output after proper operation has been confirmed.
Ensure that the remote release modules are not activating suppression
systems. Physically disconnect the wiring to all agent-release and pre-action-
CAUTION
sprinkler circuits if the control modules are activating suppression systems.
Restore the system to normal operating condition at the conclusion of all RRM
activations and any other functional tests.
Step
1
Press 0 Key
2
Enter Password; press "Enter" Key
3
Press 4 Key
4
Press "Scroll" Key
5
Press 7 Key
6
Press "Scroll" Key twice
7
Press 9 Key
8
Press 2 Key and then press "Enter" Key
9
Press 1, 2, 3 or 4 Key for the RRM group and then
press "Enter" Key.
10
Press "Backspace" Key (as required)
August 2013
Purpose: To manually de-activate one or more RRMs that were
activated during system testing.
Note: Each RRM must be manually de-activated via this menu
operation or a system reset before the system can be returned
to normal operating condition.
Action
3-94
Result
Initiate Menu Access
Gain access to menus
Enter Test-Menu branch
Access additional Test-Menu options
Select "Output Test" option
Access additional Outputs-Test options
Select "RRM Group"
De-activate "RRM Group Devices"
Select the applicable RRM group and deactivate.
Exit Menu System
P/N 06-236530-001