Kidde ARIES Installation, Operation And Maintenance Manual page 152

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.4.50 How to Enable Outputs on a Networked Control Unit to be Remotely
Step
1
Press 0 Key
2
Enter Password
3
Press 3 Key
4
Press "Scroll" Key
5
Press 6 Key
6
Press "Scroll" Key
7
Press 6 Key
8
Press 1 Key and then press "Enter" Key to confirm
selection.
9
Press "Backspace" Key (as required)
10
Wait until "Initializing Configuration" message
disappears from the display.
August 2013
Silenced by Another Control Unit
Purpose: To allow the silenceable outputs on a networked control unit
to be silenced by other control units in the network. This procedure
enables the outputs to be silenced as follows:
1. By any other control unit when no sub-groups are used
2. By any other control unit in the group when sub-groups are used
3. By the master mode (i.e., Group 0)
Action
3-70
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access additional options
Select "Network" option
Access additional options
Select "Silence"
Select "Enable"
Exit Menu System
Initialization complete
P/N 06-236530-001