3-2.5.2.4.40 How to Configure the Control Unit for Central-Station Operation
Step
1
Press 0 Key
2
Enter Password; press "Enter" Key
3
Press 3 Key
4
Press "Scroll" Key
5
Press 5 Key
6
Press "Scroll" Key
7
Press 4 Key
8
Press 1 Key, then press "Enter" Key to confirm
selection.
9
Press "Backspace" Key (as required)
3-2.5.2.4.41 How to Configure the Global Alarm Acknowledge
Step
1
Press 0 Key
2
Enter Password; press "Enter" Key
3
Press 3 Key
4
Press "Scroll" Key
5
Press 5 Key
6
Press "Scroll" Key
7
Press 5 Key
8
Press 1 Key to turn on Global Alarm
Acknowledgement or
Press 2 Key to turn off Global Alarm
Acknowledgement,
then press "Enter" Key to confirm selection.
9
Press "Backspace" Key (as required)
P/N 06-236530-001
Purpose: To allocate the programmable relays for off-premises signal
transmission to a central station. Programmable Relay No. 1 is
automatically configured to activate for any alarm condition, and
Programmable Relay No. 2 is automatically configured to activate for
any supervisory condition. Refer to Appendix F.
Action
Purpose: When this feature is enabled, when the operator presses the
"Acknowledge" key, all current alarms are acknowledged. If this
feature is disabled, the operator must acknowledge each alarm
individually.
Action
3-61
Result
Initiate Menu Access
Gain access to menus
Enter Set-Menu branch
Access additional Set-Menu options
Select "Globals" option
Access additional Globals-Menu options
Select "Central Station" option
Activate Central-Station option
Exit Menu System
Result
Initiate Menu Access
Gain access to menus
Enter Set-Menu branch
Access additional Se-Menu options
Select "Globals" option
Access additional Globals-Menu options
Select "Global Alarm Ack" option
Activate or Deactivate Global Alarm Acknowledge
option
Exit Menu System