Isolate Menu Functions - Kidde ARIES Installation, Operation And Maintenance Manual

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.2
3-2.5.2.2.1
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 1 Key
4
Press 1 Key
5
Press 1 Key for SLC inputs or 2 Key for SLC
outputs.
Press "Enter" Key to confirm selection.
6
Use keypad to enter single device or range of
devices to isolate.
Press "Enter" Key to confirm selection.
7
Press 1 Key and then press "Enter" Key to confirm
selection.
8
Press "Backspace" Key (as required)
9
Press "Acknowledge" Key.
P/N 06-236530-001

Isolate Menu Functions

The Isolate functions prevent the ARIES Control Unit from acting upon
signals from initiating devices or from issuing activation commands to
control unit-based and SLC-based outputs. The initiating devices and
outputs remain operational, but are disconnected from the control unit in
the sense that events reported by isolated initiating devices are ignored by
the control unit and commands to activate are ignored by isolated outputs
and control modules.
A Supervisory signal will occur after each Isolation command is executed,
and will remain in effect until all Isolation commands are subsequently
cancelled by their corresponding De-Isolation commands.
For Top-Level Isolate Menu Functions, refer to Figure 3-4. For the
complete Isolate-Menu tree, refer to Figure 3-5.
The following paragraphs list the Isolate Menu functions.
How to Isolate SLC Devices
Purpose: To prevent initiating and trouble signals from selected
SmartOne automatic detectors and monitor modules from being
processed and acted upon by the ARIES Control Unit. Also to prevent
selected SmartOne control and relay modules from carrying out
activation instructions issued by the ARIES Control Unit.
Note: An SLC device can only be isolated if it is not in either a trouble
or alarm condition.
Action
3-13
Result
Initiate menu access
Gain access to menus
Enter Isolate-Menu branch
Select "SLC Devices" option
Select "SLC Inputs" or "SLC Outputs."
Get prompt to Isolate or De-Isolate
Execute Isolation Routine for single device or
range of devices entered in Step 5.
Exit Menu System
Silence buzzer and change Supervisory LED from
flashing to steady
August 2013