Kidde ARIES Installation, Operation And Maintenance Manual page 250

Fire alarm/suppression
Table of Contents

Advertisement

Remote-Display/Annunciator
Events
Error Message
ATMAddr Not Registered On
ATMAddr PSU Fault On
ATMAddr Reset Input Fault On
ATMAddr Silence Input Fault On
ATMAddr Silenced Output Fault On
August 2013
Table 5-5. Remote-Display/Annunciator Events (Continued)
Probable Cause
The control unit has not been set up
to expect the ATM at ATM RS-485
circuit address Addr.
A loss of 24 Vdc power at Terminal
Block TB3 or an open circuit in the
monitoring circuit from the ATM's "PS
Flt" and "Com" terminals to the
normally-closed trouble contacts of
its associated remote power supply
An open circuit in wiring from the
ATM-L's "Reset" input terminal to the
associated annunciator's reset
switch. ATM-L address is Addr
An open circuit in wiring from the
ATM-L's "Silence" input terminal to
the associated annunciator's alarm-
silence switch. ATM-L address is Addr
An open circuit in wiring from the
ATM-L's "Silence" output terminal to
the associated annunciator's alarm-
silence LED. ATM-L address is Addr
Corrective Action
• Register the ATM if part of system
• Upload a new application program
• De-register the ATM if not part of
• Check the 24 Vdc power (Terminal
• Ensure that the ATM Address
• Refer to ATM Installation Manual,
• Refer to ATM Installation Manual,
• Check for 24 Vdc power at ATM
• Look for discontinuity in wiring to
• Check for trouble with third-party
• Refer to ATM Installation Manual,
• Look for discontinuity in wiring to
• Check for missing 10k end-of-line
• Refer to ATM Installation Manual,
• Look for discontinuity in wiring to
• Check for missing 10k end-of-line
• Refer to ATM Installation Manual,
• Look for discontinuity in wiring to
• Check for missing 20k supervising
5-20
configuration. See
Paragraph 3-2.5.2.4.57. If this
procedure is insufficient, the
following procedure must also be
conducted:
that includes the previously
unregistered ATM.
system configuration. See
Paragraph 3-2.5.2.4.58.
Block TB3)and RS-485
communications wiring (Terminal
Blocks TB1 and TB2) from the
control unit to the ATM
Switch S1 is set correctly.
P/N 06-236179-002.
P/N 06-236179-002.
Terminal Block TB3.
remote-power-supply trouble
contacts. Jumper these terminals if
you are using the ARIES Control
Unit to power the ATM.
remote power supply
P/N 06-236179-002.
reset switch
resistor.
P/N 06-236179-002.
alarm-silence switch
resistor.
P/N 06-236179-002.
alarm-silence LED (if used)
resistor if alarm-silence LED not
used.
P/N 06-236530-001