Kidde ARIES Installation, Operation And Maintenance Manual page 107

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.3.10 How to List a Range of SLC Device Voltages
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 2 Key
4
Press "Scroll" Key Twice
5
Press 7 Key
6
Press 1 Key
7
Enter Start Address and End Address.
Use XXX format for address.
Press "Enter" Key to confirm address selection.
8
Press "Scroll" Key (as required)
9
Press "Backspace" Key (as required)
3-2.5.2.3.11 How to List a Range of SLC Devices' 9-Volt Levels
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 2 Key
4
Press "Scroll" Key Twice
5
Press 7 Key
6
Press 2 Key
7
Enter Start Address and End Address.
Use XXX format for address.
Press "Enter" Key to confirm address selection.
8
Press "Scroll" Key
9
Press "Backspace" Key (as required)
P/N 06-236530-001
Purpose: To view the SLC line voltages for a range of initiating and/or
control devices.
Action
Purpose: To view the internal power-supply voltages for a range of SLC
initiating and/or control devices.
Action
3-25
Result
Initiate menu access
Gain access to menus
Enter List-Menu branch
Access additional options
Access "Voltages" option
Select "Line Voltage"
View devices' line voltages
Format for devices is:
Addr
Type
Move through selected devices
Exit Menu System
Result
Initiate menu access
Gain access to menus
Enter List-Menu branch
Access additional options
Access "Voltages" option
Select "9 volt"
View devices' 9-Volt levels
Format for devices is:
Addr
Type
9-Volt Level
Move through selected devices
Exit Menu System
Voltage
August 2013