Kidde ARIES Installation, Operation And Maintenance Manual page 237

Fire alarm/suppression
Table of Contents

Advertisement

Control-Unit-Based-Output Events
Error Message
SG3 Short Circuit Trouble On
SG4 Open Circuit Trouble On
SG4 Short Circuit Trouble On
SLC Events
Error Message
Addr Switch Not Set On AlarmLine
Module
Addr 24 Vdc Failure Signal/ Sounder
P/N 06-236530-001
Table 5-2. Control-Unit-Based-Output Events (Continued)
Probable Cause
Short circuit in field wiring connected
to main circuit board TB7. Combo-1
Circuit is configured as a NAC.
Open circuit in field wiring connected
to main circuit board TB6. Combo-2
Circuit is configured as a NAC.
Short circuit in field wiring connected
to main circuit board TB6. Combo-2
Circuit is configured as a NAC.
Table 5-3. SLC Events
Probable Cause
An incorrect configuration for the
AAM at address Addr
Failure of the DC to DC converter in
the ASM at address Addr
• Troubleshoot Combo-1 wiring by
• Check for missing 10k end-of-line
• Look for discontinuity in Combo-2
• Troubleshoot Combo-2 wiring by
Corrective Action
• Check the configuration settings for
• Refer to AlarmLine Installation,
• Refer to ASM Installation
• Check 24 Vdc power connections to
• Ensure that the ASM's Jumper P1
• Replace the ASM if steps above are
5-7
Corrective Action
breaking-up circuit to isolate short
circuit to specific leg.
resistor.
field wiring.
breaking-up circuit to isolate short
circuit to specific leg.
the AAM. Re-configure and upload
the correct configuration.
Operation, and Maintenance
Manual, P/N 73.04
Instructions, P/N 06-235717-001.
ASM.
and Switch S1 are set for 24 Vdc
operation
unsuccessful
August 2013