Kidde ARIES Installation, Operation And Maintenance Manual page 138

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.4.30 How to De-Activate Alarm Verification for Smoke Detectors
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 3 Key
4
Press "Scroll" Key
5
Press 4 Key
6
Press "Scroll" Key
7
Press 5 Key
8
Press 2 Key and then press "Enter" Key to confirm
selection.
9
Use keypad to enter single address or range of
smoke-detector addresses for verification to be
de-activated.
Press "Enter" Key to confirm selection.
10
Press "Backspace" Key (as required)
11
Wait until "Initializing Configuration" message
disappears from the display.
3-2.5.2.4.31 How to Activate Positive-Alarm Sequence for Smoke Detectors
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 3 Key
4
Press "Scroll" Key
5
Press 4 Key
6
Press "Scroll" Key
7
Press 6 Key
8
Press 1 Key and then press "Enter" Key to confirm
selection.
9
Use keypad to enter single address or range of
smoke-detector addresses for positive-alarm
sequence.
Press "Enter" Key to confirm selection.
10
Press "Backspace" Key (as required)
11
Wait until "Initializing Configuration" message
disappears from the display.
August 2013
Purpose: To de-activate alarm-verification for one or more smoke
detectors. See Paragraph 3-2.5.5.3 for the description of alarm
verification.
Action
Purpose: To activate positive-alarm sequence for one or more smoke
detectors. See Paragraph 3-2.5.5.1 for the description of positive-
alarm sequence.
Action
3-56
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access additional options
Select Programming option
Access additional options
Select "Alarm-Verification" option
De-activate alarm verification
Specify addresses for verification to be de-
activated
Exit Menu System
Resume Normal Operations
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access additional options
Select Programming option
Access additional options
Select "Positive-Alarm Sequence"
Activate positive-alarm sequence
Specify addresses for Positive-Alarm Sequence
Exit Menu System
Resume Normal Operations
P/N 06-236530-001