Kidde ARIES Installation, Operation And Maintenance Manual page 158

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.4.59 How to Reset Remote-Annunciator Modules
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 3 Key
4
Press "Scroll" Key
5
Press 7 Key
6
Press 3 Key
7
Press 1 Key
8
Press "Backspace" Key (as required)
3-2.5.2.4.60 How to Enable Battery Supervision
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 3 Key
4
Press "Scroll" Key three times
5
Press 9 Key (Installer)
6
Press 3 Key
7
Press 1 Key, then press "Enter" Key
8
Press "Backspace" Key (as required)
3-2.5.2.4.61 How to Disable Battery Supervision
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 3 Key
4
Press "Scroll" Key three times
5
Press 9 Key (Installer)
6
Press 2 Key, then press "Enter" Key
7
Press "Backspace" Key (as required)
8
Press "Backspace" Key (as required)
August 2013
Purpose: To remove any off-normal indications from remote-
annunciator modules that did not clear after a reset command
Action
Purpose: To restore battery supervision that was disabled by the
procedure in Paragraph 3-2.5.2.4.61.
Action
Purpose: To disable battery supervision for systems that are not using
a standby battery for secondary power.
Action
3-76
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access additional options
Select "Control Modules" option
Select Reset ATM/RDCM
Execute reset command
Exit Menu System
Result
Initiate Menu Access
Gain access to menus
Enter Set-Menu branch
Access additional Set-Menu options
Select "Battery" option
Select "Disable Battery" option
Select "Enable Battery" Connection
Exit Menu System
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access additional Set-Menu options
Select "Disable-Battery" option
Select Disable Battery Connection
Exit Menu System
Exit Menu System
P/N 06-236530-001