Kidde ARIES Installation, Operation And Maintenance Manual page 116

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.4.5
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 3 Key
4
Press 2 Key
5
Press 1 Key for Port J8 (RS-232 A) or
Press 2 Key for Port J3 (RS-232 B)
6
Press 1 Key for a Printer or
Press 2 Key for IIM or
Press 3 Key for ICM
Press "Enter" Key to confirm selection.
7
Press "Backspace" Key (as required)
8
Wait until "Initializing Configuration" message
disappears from the display.
3-2.5.2.4.6
August 2013
How to Configure the Communications Ports
Purpose: To change the RS-232 communications ports for use with a
serial printer, The laptop or desktop computer (PC), and/or terminal
emulator. Both RS-232 communications ports default to interface with
either a PC or a terminal emulator with the following communications
settings: 9600 Baud Rate, No Parity, 8-Bit Word Length, 1 Start Bit, 1
Stop Bit.
Action
How to Change an SLC Device Address
Purpose: To create or change an SLC device address using the ARIES
keypad. All SLC devices are shipped with the default address of 000.
This address must be changed to a valid address in the range 1 to 255
before the device can be used on the SLC. Only one device with
address 000 can be connected to the SLC when using this procedure to
initially address a new device. This procedure can also be used to re-
address a previously addressed device. Be sure to de-register the
previous address after the device is re-addressed.
Note: An SLC device can only have its address changed if it is not in
either a trouble or alarm condition.
3-34
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access "Port Control" option
Select port to configure
Select optional device being used
Exit Menu System
P/N 06-236530-001