Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 3 Key
4
Press "Scroll" Key
5
Press 4 Key
6
Press 3 Key
7
Wait until "AutoLearning Devices on SLC"
message disappears from the display.
3-2.5.2.4.27 How to Obtain the Manufacturer's Code
Step
1
Press and hold down the 4 key
3-2.5.2.4.28 How to Run the AutoSetup Procedure
P/N 06-236530-001
Action
Purpose: If the owner's or installer's code for the panel is lost, the
installer or owner must use this command to obtain the manufacturer's
code. They must then contact Kidde Technical Support and recite this
code to the Technical Support Representative in order to receive a
temporary password. The installer or owner can login with this
password for up to 5 days and should change the password
immediately.
Action
Purpose: The AutoSetup Procedure executes a Registration Procedure
for all unregistered SLC devices and, in addition, configures the system
for operation as a waterless fire-suppression system. The following
operating characteristics are assigned to the ARIES Control Unit and its
associated SLC devices.
1. SLC Device Assignments
Automatic activation of the extinguishing system will be via
crossed-zoned alarm-initiating signals generated by combinations
of automatic initiating devices assigned to any of the first 100
addresses on the SLC. One half of the crossed-zoned alarm-
initiating system will consist of any automatic initiating device
addressed within the range of 001 through 050. The other half of
the crossed-zoned automatic-initiating system will consist of any
automatic initiating device addressed within the range of 051
through 100.
Spot-type detectors from each half of the crossed-zoned detection
system must be alternated throughout the protected area.
The extinguishing system will be manually activated by monitor
modules
(i.e.,
Operation of a manual-release station will cause all alarm and
shutdown devices to operate as if the system had operated
automatically and will cause an immediate activation of the fire-
extinguishing system. Operation of a manual-release station will
override the operation of all abort switches. Each monitor module
3-53
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access additional options
Select Programming option
Activate "AutoLearn"
Exit Menu System and Resume Normal
Operations.
Result
The Manufacturer's Code displays. Write down
this code and contact Kidde Technical Support.
AIs)
configured
as
manual-release
stations.