Figure 2-22 shows a combination circuit wired for releasing. Refer to Appendix C for
further information.
2-11
RELEASING CIRCUITS
The ARIES has two releasing circuits that can be configured to actuate extinguishing systems
through any of the following ways:
•
Single actuator assembly
•
Single control head or solenoid valve
•
Two series-supervised, parallel-actuated control heads or solenoid valves.
The release circuits are labeled Release1 and Release2 and have field-wiring connections that
terminate at TB12 and TB11, respectively.
Ensure that all releasing devices are physically disconnected from the releasing
circuits before performing any system testing or maintenance.
WARNING
2-11.1
Releasing Circuits for Actuator Assembly
Actuator assembly is a non-explosive device. Do not remove the shorting cap
from the cable connector until the field-wiring connections are to be made.
Physical abuse or static-electricity discharge could cause inadvertent actuator
WARNING
actuation. The installer must establish a common electrical potential with the
actuator assembly before either removing or inserting the shorting cap.
Figure 2-23 shows an actuator assembly connected to a releasing circuit. Each releasing
circuit is capable of actuating one actuator assembly.
August 2013
Combo 1 or
Combo 2
1
2
3
4
TB7 or
TB6
Supervised and Power-Limited
Figure 2-22. Combination Circuit used as Releasing Circuit
Red
Blk
In-Line Releasing Device (P/N 06-220023-001)
(Must be close nippled to solenoid enclosure)
2-22
Solenoid
(Refer to Appendix C)
P/N 06-236530-001