Kidde ARIES Installation, Operation And Maintenance Manual page 173

Fire alarm/suppression
Table of Contents

Advertisement

There is no indication at the control unit that an output is activated. Be sure to
de-activate the output after proper operation has been confirmed.
Ensure that the control modules are not activating suppression systems or
controlling critical facility operations such as computer power. Physically
disconnect the wiring to all agent-release and pre-action-sprinkler circuits and
CAUTION
bypass all affected power-off circuits before activating any control modules if
the control modules are activating suppression systems or are shutting off
power. Restore the system to normal operating condition at the conclusion of
all control-module activations and any other functional tests.
Step
1
Press 0 Key
2
Enter Password; press "Enter" Key
3
Press 4 Key
4
Press "Scroll" Key
5
Press 7 Key
6
Press "Scroll" Key twice
7
Press 8 Key
8
Enter starting SLC address and ending SLC
address.
Use XXX format for addresses.
Press "Enter" Key to confirm address range of
control modules to de-activate.
9
Press 2 Key and then press "Enter" Key
10
Return to Step 8 and make another selection
(optional)
11
Press "Backspace" Key (as required)
3-2.5.2.5.14 How to Activate Remote Release Modules
There is no indication at the control unit that an output is activated. Be sure to
de-activate the output after proper operation has been confirmed.
Ensure that the remote release modules are not activating suppression
systems. Physically disconnect the wiring to all agent-release and pre-action-
CAUTION
sprinkler circuits if the control modules are activating suppression systems.
Restore the system to normal operating condition at the conclusion of all RRM
activations and any other functional tests.
P/N 06-236530-001
Action
Purpose: To manually activate one or more remote release modules
during system testing to confirm the proper operation.
Note: All remote release modules must be manually de-activated via
a menu operation or a system reset before the system can be
returned to normal operating condition.
3-91
Result
Initiate Menu Access
Gain access to menus
Enter Test-Menu branch
Access additional Test-Menu options
Select "Output Test" option
Access additional Outputs-Test options
Select "SLC Outputs"
Specify range of control modules to de-activate.
Initiate control-module de-activation specified in
Step 8
De-activate additional control modules
Exit Menu System
August 2013