3-3.5

Event Output Control (EOC)

A confirmed event at any control unit can create output control, including extinguishing-
system activation, in any of the following ways:
The default operation for event-output control is globally to all control units in the
network.
Any control unit can create local output control, including extinguishing system
activation, only to its directly controlled peripheral devices and output circuits. Refer to
the ARIES Configuration Software User's Guide for information on configuring the EOC
for network events.
3-3.6

Configuration Uploads/Downloads

The ARIES Configuration Program can upload and download configuration settings and
application programs via one control unit to and from any other control unit in the
network.
Refer to the ARIES Configuration Software User's Guide for information on configuring
the different network settings.
3-3.7

Menu Routines

Menu routines for a control unit can be activated:
3-3.7.1
August 2013
Locally to its directly controlled peripheral devices and output circuits only
Selectively to peripheral devices and output circuits controlled by a subset of
networked control units
Note: This requires EOC code on the remote control units to activate their local
outputs.
Globally to peripheral devices and output circuits controlled by all control units in
the network.
Note: This requires EOC code on the remote control units to activate their local
outputs.
Directly from its keypad/display
Selectively from a subset of the networked control units
Globally from all control units in the network

ACCESSING REMOTE NODE MENUS VIA KEYPAD

When a password is entered on an active network system, the prompt shown in
Figure 3-57 is displayed.
PRESS ENTER TO SELECT THE LOCAL NODE
OR ENTER NETWORK NODE NO. (1 - 32)
Figure 3-57. Network Node Prompt
Local Node Access - Press the <Enter> key to select the local node; the
response shown in Figure 3-58 is displayed.
1: ISOLATE
3: SET
Figure 3-58. Top-level Menu Selections
Remote Node Access - Enter the node number then press the <Enter> key; in
response, the password prompt for the remote node is displayed.
2: LIST
4: TEST
3-126
P/N 06-236530-001