Input Configuration; Status Indications - Kidde Excellence Series Installation Sheet

Intelligent addressable single input module
Hide thumbs Also See for Excellence Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Wiring the module
Connect the loop wires as shown below. See Table 2 for
recommended cable specifications.
Table 1: Loop connection
Terminal
Description
B−
Negative line (–)
A−
Negative line (–)
B+
Positive line (+)
A+
Positive line (+)
Table 2: Recommended cable specifications
Cable
Specification
Loop
0.13 to 3.31 mm² (26 to 12 AWG) shielded or
unshielded twisted-pair (52 Ω and 500 nF max.)
Input [1]
0.5 to 4.9 mm² (20 to 10 AWG) shielded or
unshielded twisted-pair
[1] 160 m max. distance from input terminal to end of line.
See Figure 2 and "Input configuration" below for input
connections.
Addressing the module.
Set the device address using the DIP switch. The address
range is 001-128.
The configured device address is the sum of the switches in
the ON position, as shown in the figures below.
Device address 008

Input configuration

The module input mode is configured at the control panel
(Field setup > Loop device configuration).
The available modes are:
Normal
Bi-Level
Normally Open (NO)
Normally Closed (NC)
The resistors required for each mode are shown below.
Table 3: Input configuration resistors
End-of-line
resistor
Mode
15 kΩ, ¼ W, 1%
Normal
X
Bi-Level
X
NO
X
NC
X
[1] With activation switch.
2 / 31
Device address 112
Series
Series
resistor [1]
resistor [1]
2 kΩ, ¼ W, 5%
6.2 kΩ, ¼ W, 5%
X
X
X
Normal mode
Normal mode is compatible for use in installations requiring
EN 54-13 compliance.
Input activation characteristics for this mode are shown in the
table below.
Table 4: Normal mode
State
Short circuit
Active 2
High resistance fault
Quiescent
Open circuit
Bi-Level mode
Bi-Level mode is not compatible for use in installations
requiring EN 54-13 compliance.
Input activation characteristics for this mode are shown in the
table below.
Table 5: Bi-Level mode
State
Short circuit
Active 2 [1]
Active 1
Quiescent
Open circuit
[1] Active 2 takes priority over Active 1.
Normally Open mode
In this mode a short circuit is interpreted as active at the
control panel (only open circuit faults are notified).
Normally Closed mode
In this mode an open circuit is interpreted as active at the
control panel (only short circuit faults are notified).

Status indications

The device status is indicated by the Device status LED
(Figure 1, item 7), as shown in the table below.
Table 6: Device status LED indications
State
Isolation active
Device fault
Test mode
Located device [1]
Communicating [2]
[1] Indicates an active Locate Device command from the control panel.
[2] This indication can be disabled from the control panel or the
Configuration Utility application.
The input status is indicated by the Input status LED (Figure 1,
item 5), as shown in the table below.
P/N 12-0201-501-4000-01 • ISS 21NOV23
Activation value
< 0.3 kΩ
0.3 kΩ to 7 kΩ
7 kΩ to 10 kΩ
10 kΩ to 17 kΩ
> 17 kΩ
Activation value
< 0.3 kΩ
0.3 kΩ to 3 kΩ
3 kΩ to 7 kΩ
7 kΩ to 27 kΩ
> 27 kΩ
Indication
Steady yellow LED
Flashing yellow LED
Fast flashing red LED
Steady green LED
Flashing green LED