Trim Ring; Smartone Detectors - Kidde ARIES Installation, Operation And Maintenance Manual

Fire alarm/suppression
Table of Contents

Advertisement

Latch
KIDDE-FENWAL, INC.
400 MAIN STREET, ASHLAND, MA 01721
TEL: (508) 881-2000 FAX: (508) 881-8920
MODEL: OCC
Front View with Door Open
1-3.6

Trim Ring

A trim ring (Figure 1-11) is available to semi-flush mount the control unit.
1-4

SMARTONE DETECTORS

The ARIES uses the SmartOne™ Series of intelligent smoke and heat detectors. These detectors
have their own data transceivers, micro-controllers, micro-controller memory, and algorithms
that allow the detectors to determine whether a normal, pre-alarm, alarm, or trouble condition
exists at their monitoring locations. Each detector continuously transmits its current status to
the ARIES through the signaling line circuit, and responds to control unit polling and inquiries by
the address that is set in the detector using the Handheld Programmer, P/N 74-200013-001, or
using the ARIES's display. The pre-alarm and alarm thresholds are programmable for each
detector.
A blinking LED on an intelligent detector indicates communications between the detector and
the control unit.
August 2013
R
Figure 1-10. Fiber Optic Converter Card
Figure 1-11. Trim Ring
8"
5-1/2"
9/32" Diameter
+
+
-
-
24V
RxN
TxN
RxI
TxI
RxN
TxN
RxI
TxI
TB1
B2N
B1N
A1N
B1I
A1I
Q1
D1
Q2
D3
Q3
D5
Q4
D7
9/32" Diameter
1-1/2 in.
All Around
14-9/16 in.
19-5/16 in.
1-10
2-9/32"
8"
TB2
A2N
B2I
A2I
1-1/4"
1-1/16"
½" & ¾"
Knockout (2)
Side View
P/N 06-236530-001
Module
Ground
Lug