3-2.5.2.4.65 How to De-Register High-Sensitivity Smoke Detectors (HSSDs)
Step
1
Press 0 Key
2
Enter Password
3
Select the local node then press "Enter" or a
select a remote node number, press "Enter" then
enter the remote node's password.
4
Press 3 Key
5
Press "Scroll" Key twice
6
Press 8 Key
7
Press 4 Key
8
Use keypad to enter single HSSD or range of
HSSDs to de-register.
Press "Enter" Key to confirm selection.
9
Press "Backspace" Key (as required)
10
Wait until "Initializing Configuration" message
disappears from the display.
3-2.5.2.5
3-2.5.2.5.1
Physically disconnect the wiring to all agent-release and pre-action-sprinkler
circuits and activate the global-isolate-outputs routine before testing any SLC
initiating devices. Restore the system to normal operating condition at the
CAUTION
conclusion of these tests and any other functional tests that were performed.
August 2013
Purpose: To remove HSSDs connected to an IIM from the ARIES
Control Unit's configuration memory.
Action
Test Menu Functions
The Test functions enable service personnel to test the SmartOne initiating
devices for the ability to transmit alarm signals. You can also perform
alarm-simulation tests for the system's application program and can
command on control modules connected to the SLC.
Test Commands are used to initiate a walk test.
Refer to Figure 3-4 for the Top-Level Test-Menu Functions. Refer to
Figure 3-5 for the complete Test-Menu tree.
How to Test SLC Initiating Devices
Purpose: To manually test the capability of one or more SmartOne
initiating devices (i.e., detectors and monitor modules) to generate
and transmit alarm signals that can be properly interpreted and
processed by the ARIES Control Unit.
Note: The ARIES Control Unit automatically runs this test once a day
for all the configured initiating devices on the SLC. The most
current test results for all initiating devices are stored in the
SLC Test Results log.
3-80
Result
Initiate menu access
Gain access to menus
Access applicable control unit (if networked
system)
Enter Set-Menu branch
Access additional options
Select "HSDs" option
Select de-register HSDs
Specify single HSSD or range of HSSDs to be de-
registered
Exit Menu System
Initialization complete