Kidde ARIES Installation, Operation And Maintenance Manual page 117

Fire alarm/suppression
Table of Contents

Advertisement

Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 3 Key
4
Press 3 Key
5
Press 1 Key
6
Use keypad to enter default address 000 for new
device or enter existing address to be changed.
Press "Enter" Key to confirm selection.
7
Use keypad to enter target address for new
device or enter altered address for existing
device.
Press "Enter" Key to confirm selection.
8
Press "Backspace" Key (as required)
9
Wait until "Initializing Configuration" message
disappears from the display.
3-2.5.2.4.7
P/N 06-236530-001
Action
How to Change an Ionization Detector's Pre-Alarm and Alarm
Thresholds
Purpose: To change the pre-alarm and alarm thresholds of one or more
ionization detectors. The ionization detector is UL Listed and FM
Approved for alarm reporting anywhere within the obscuration range of
0.5 to 1.5 percent per foot when used for an open-area application.
Alarm thresholds can be set in 0.1 percent-per-foot increments. A pre-
alarm threshold can also be set anywhere within the obscuration range
of 0.5 to 1.4 percent per foot, but must be less than the detector's alarm
threshold. Two additional alarm-reporting ranges are defined for special
applications. The in-duct range refers to detector placement in an air
duct. The DH-2000 range refers to detector placement in a DH-2000
Duct Housing with associated sampling tubes to monitor the air in either
a supply- or return-air duct. The alarm ranges for these special
applications are as follows:
Application
Induct
DH-2000
Ionization detectors can be automatically programmed to change
alarm thresholds by time of day if they are configured for day/night
operation. The night alarm thresholds must be less than the
corresponding day thresholds.
3-35
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access "SLC Devices" option
Select "Device Address Change"
Specify address to be changed
Specify target address
Exit Menu System
Pre-Alarm/Alarm Range (%/foot)
0.5 - 1.0
0.5 - 1.0
August 2013