Kidde ARIES Installation, Operation And Maintenance Manual page 100

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.2.10 How to Globally De-Isolate Initiating Devices
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 1 Key
4
Press "Scroll" Key
5
Press 4 Key
6
Press 1 Key and then press "Enter" Key to confirm
selection.
7
Press 2 Key and then press "Enter" Key to confirm
selection.
8
Press "Backspace" Key (as required)
3-2.5.2.2.11 How to Globally Isolate System Outputs
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 1 Key
4
Press "Scroll" Key
5
Press 4 Key
6
Press 2 Key and then press "Enter" Key to confirm
selection.
7
Press 1 Key and then press "Enter" Key to confirm
selection.
8
Press "Backspace" Key (as required)
9
Press "Acknowledge" Key
August 2013
Purpose: To enable the ARIES Control Unit to process initiating and
trouble signals from all previously-isolated SLC-based and IIM-based
initiating devices
Action
Purpose: To prevent all SLC-based and control-unit-based outputs
(including relays) from being activated by the ARIES Control Unit
Action
3-18
Result
Initiate menu access
Gain access to menus
Enter Isolate-Menu branch
Access additional options
Select "Global Isolate" option
Select "Inputs"
Execute De-Isolation Routine for all initiating
devices
Exit Menu System
Result
Initiate menu access
Gain access to menus
Enter Isolate-Menu branch
Access additional options
Select "Global Isolate" option
Select "Outputs"
Execute Isolation Routine for all output devices
and circuits
Exit Menu System
Silence buzzer and change Supervisory LED from
flashing to steady
P/N 06-236530-001