Kidde ARIES Installation, Operation And Maintenance Manual page 238

Fire alarm/suppression
Table of Contents

Advertisement

SLC Events
Error Message
Addr 9V DC Fault On Device Type
Addr Abort Trouble On Monitor
Module
Addr Alarm Test Fail Device Type
August 2013
Table 5-3. SLC Events (Continued)
Probable Cause
A failure of the internally generated
9-Volt power supply for the
SmartOne smoke or heat detector at
address Addr.
The abort switch being monitored by
the AI at address Addr is activated
and the system is not in alarm
An initiating device (i.e., automatic
detector or monitor module) at
address Addr failed a device test. The
initiating device was unable to send
an acceptable alarm-test signal when
requested by the control unit.
5-8
Corrective Action
• Check SLC wiring. Refer to
Paragraph 2-8. Ensure that wiring-
resistance and -capacitance
limitations have not been
exceeded.
• Visually inspect the detector to
ensure that its red LED is flashing.
Use Handheld Programmer to test
the device if the LED is not
flashing. Refer to Appendix D.
Replace the detector if it fails the
Handheld-Programmer test.
• List the automatic initiating
device's 9-Volt level. Refer to
Paragraph 3-2.5.2.3.11. Replace
the device if the 9-Volt level varies
by + / - 1.0 (nom.) Vdc volts.
• Conduct an initiating device test on
the automatic detector. See
Paragraph 3-2.5.2.4.5
• Activate and confirm a proper
alarm response from the detector.
• Replace the device if any of the
above tests are unsuccessful.
• Check abort switch for mechanical
failure
• Globally isolate all outputs. See
Paragraph 3-2.5.2.2.9.
• Disconnect device from SLC and
visually inspect for damage. Clean
if automatic detector.
• Use Handheld Programmer to test
the device. Refer to Appendix D.
Reconnect device to SLC.
• Conduct an initiating device test on
the initiating device. Repeat this
procedure at least 3 times. See
Paragraph 3-2.5.2.4.5. Check
wiring if test results are
inconsistent. Refer to
Paragraph 2-8. Ensure that wiring-
resistance and -capacitance
limitations have not been
exceeded.
• Activate and confirm a proper
alarm response from the initiating
device
• Replace device if any of above tests
is unsuccessful.
• Globally de-isolate all outputs. See
Paragraph 3-2.5.2.2.9.
P/N 06-236530-001