Combination Circuits; 2-10.1 Combination Circuits Used As Nacs - Kidde ARIES Installation, Operation And Maintenance Manual

Fire alarm/suppression
Table of Contents

Advertisement

Use Figure 2-19 to estimate the maximum length of wire as a function of notification-appliance
current for both NACs.
12000
11500
11000
10500
10000
9500
9000
8500
8000
7500
7000
6500
6000
5500
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0
0.0
2-10

COMBINATION CIRCUITS

The ARIES Control Unit has two combination circuits that can be used either as notification-
appliance circuits (NACs) or as releasing circuits for solenoid valves. The combination circuits
are labeled Combo1 and Combo2. These circuits have field-wiring connections that terminate at
TB7 and TB6, respectively.
2-10.1
Combination Circuits used as NACs
Each combination circuit can supply up to 1.5 A of current at a nominal 24 Vdc for
polarized notification appliances when configured as a NAC. Total current output of the
ARIES power supply must not exceed 5.4 A.
Both combination circuits are supervised and power limited when configured as NACs.
They are compatible with conventional, UL-Listed, 24-Vdc notification appliances. They
can also be used with the following synchronizable horns and strobes:
The NS Series notification appliances provide the option to use silenceable horns and
non-silenceable strobes on the same NAC. Refer to the ARIES Programmer's Guide to
configure one or both combination circuits as NACs and to configure them for use with
the NS Series notification appliances.
August 2013
0.1
0.2
0.3
0.4
0.5
Figure 2-19. Wiring Length vs. Notification-Appliance Current
MT Series Multi-Tone Horns and Horn/Strobes
NS Series Horn/Strobes
NH Series Horns
RSS(P) Series Strobes
0.6
0.7
0.8
0.9
1
NAC Current (A)
2-20
1.1
1.2
1.3
1.4
1.5
P/N 06-236530-001

Advertisement

Table of Contents
loading

Table of Contents