Kidde ARIES Installation, Operation And Maintenance Manual page 242

Fire alarm/suppression
Table of Contents

Advertisement

SLC Events
Error Message
Addr Offset Trouble On LaserNET
Interface Module
Addr Output Relay Fault Addressable
Relay
Addr Output Relay Fault
Signal/Sounder
August 2013
Table 5-3. SLC Events (Continued)
Probable Cause
The PALM at address Addr is
reporting an offset problem with the
HSSD that it is monitoring. This is
probably a problem with the
background obscuration level in the
area of the HSSD.
The AO at address Addr failed to
activate upon receipt of an activation
command
The ASM at address Addr failed to
activate upon receipt of an activation
command
5-12
Corrective Action
• Work with the end user to improve
the air quality in the HSSD
location.
• Check the PALM-to-HSSD
connections
• Use OCS to troubleshoot the HSSD
• Refer to HSSD Installation/
Maintenance Manual, P/N 89.200,
for guidance.
Caution:
Be sure to bypass the shutoff to
equipment controlled by the AO
before functionally testing this
device.
• Check SLC wiring. Refer to
Paragraph 2-8. Ensure that wiring-
resistance and -capacitance
limitations have not been
exceeded.
• Visually inspect the AO to ensure
that its red LED is flashing. Use
Handheld Programmer to test the
device if the LED is not flashing.
Refer to Appendix D. Replace the
AO if it fails the Handheld-
Programmer test.
• Functionally test the existing or
replaced AO via the procedure in
Paragraph 3-2.5.2.6. Replace the
AO if it fails the functional test.
• Functionally re-test the AO for all
configured actuation scenarios.
• Check SLC wiring. Refer to
Paragraph 2-8. Ensure that wiring-
resistance and capacitance
limitations have not been
exceeded.
• Visually inspect the ASM to ensure
that its red LED is flashing. Use
Handheld Programmer to test the
device if the LED is not flashing.
Refer to Appendix D. Replace the
ASM if it fails the Handheld-
Programmer test.
• Functionally test the existing or
replaced ASM via the procedure in
Paragraph 3-2.5.2.6. Replace the
ASM if it fails the functional test.
• Functionally re-test the ASM for all
configured actuation scenarios.
P/N 06-236530-001