3-2.5.2.5.3
Physically disconnect the wiring to all agent-release and pre-action-sprinkler
circuits before walk testing any SLC initiating devices. Restore the system to
normal operating condition at the conclusion of these tests and any other
CAUTION
functional tests that were performed.
Step
1
Press 0 Key
2
Enter Password; press "Enter" Key
3
Press 4 Key
4
Press 5 Key
5
Press 3 Key
6
Enter starting SLC address and ending SLC
address.
Use XXX format for addresses.
Press "Enter" Key to confirm address range to
walk test.
7
Press "Backspace" Key (as required)
8
Press "Acknowledge" Key
9
Message
"Walk Test: On
Normal Operation Test"
appears on the display
10
Initiate an alarm from every device specified in
Step 6.
Warning:
Do not initiate more than one alarm from any
initiating device during a walk test.
The address and device type of each initiating
device momentarily appears on the display after
it is walk tested.
11
Conclude walk test after every initiating device
specified in Step 6 has been alarmed. Press the
"Reset" Switch or refer to Paragraph 3-2.5.2.5.4
12
List the results of the Walk Test by referring to
Paragraph 3-2.5.2.3.5
P/N 06-236530-001
How to Run a Silent Walk Test
Purpose: To suspend normal system operation for functional testing of
one or more SmartOne initiating devices.
The ARIES Control Unit will operate identically as described in
Paragraph 3-2.5.2.5.2 when in a silent walk-test mode, except that it
will not energize the outputs programmed for walk-test activation.
Action
3-83
Result
Initiate Menu Access
Gain access to menus
Enter Test-Menu branch
Select "Walk Test" option
Select Silent Walk Test option
Specify range of SLC initiating devices to be walk
tested.
Exit Menu System
Make "Trouble" LED light steadily and silence
buzzer
System is ready for walk test
Conduct walk test
A successful device test will be indicated by a
"Passed" message in the "Walk-Test" Log. An
unsuccessful device test will be indicated by a
"Failed" message. Functionally test any devices
that report a failure to confirm whether or not
they are operational. Replace any devices that fail
a functional test.