Owner locations are not assigned during the AutoSetup Procedure. The Abort
operation in this setup is not UL Listed.
CAUTION
August 2013
with address within the range of 101 through 105 will be assigned
as a manual-release station.
Abort switches will, when operated, interrupt the countdown delay
for the activation of the extinguishing system and prevent the
operation of any alarms and control functions associated with the
discharge of the extinguishing agent. The abort switches must be
momentary, dead-man-type devices that require a constant force
to remain engaged and active. Abort switches will be configured to
reset the countdown timer to the full delay period. Each monitor
module with address within the range of 106 through 110 will be
assigned as an abort station.
Each AO output module with address within the range of 111 to 115
will be assigned as a pre-alarm output point.
Each AO output module with address within the range of 116 to 120
will be assigned as a pre-release output point.
Each AO output module with address within the range of 121 to 125
will be assigned as a release output point.
2. Sequence of Operation
The ARIES will progress through the pre-alarm, pre-release, and
release states as defined in Paragraph 3-2.5.8.1. The time delay
between the pre-release and the release states will be 30 seconds.
3. Control-Unit-Based Outputs Assignments
Control-unit-based outputs will be assigned to the pre-alarm, pre-
release, and release states as follows:
Pre-Alarm State
NAC No. 1 (steady activation)
programmable Relay No. 1
the owner-location field on the LCD will display the word "Pre-
Alarm"
Pre-Release State
NAC No. 2 (steady activation)
programmable Relay No. 2
the owner-location field on the LCD will display the word "Pre-
Release" concurrently with the continuously-decremented
countdown timer
deactivate NAC No. 1
Release State
Release Circuit No. 1
Release Circuit No. 2
Combination NAC/Releasing Output No. 1 as a NAC (steady
activation)
Combination NAC/Releasing Output No. 2 as a release circuit
programmable Relay No. 3
the owner-location field on the LCD will display the word
"Agent Release"
3-54