Kidde ARIES Installation, Operation And Maintenance Manual page 170

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.5.10 How to Activate Control-Unit-Based Outputs
There is no indication at the control unit that an output is activated. Be sure to
de-activate the output after proper operation has been confirmed.
Ensure that the outputs will not activate suppression systems or critical facility
operations such as computer power. Physically disconnect all agent-release and
CAUTION
pre-action-sprinkler circuits and bypass all affected power-off circuits before
activating any outputs if the outputs are activating suppression systems or are
shutting off power. Restore the system to normal operating condition at the
conclusion of all output activation and any other functional tests.
Step
1
Press 0 Key
2
Enter Password; press "Enter" Key
3
Press 4 Key
4
Press "Scroll" Key
5
Press 7 Key
6
Press 1 Key for NAC 1, or
Press 2 Key for NAC 2, or
Press 3 Key for Combo 1, or
Press 4 Key for Combo 2, or
Press 5 Key for Release 1, or
Press 6 Key for Release 2, or
Press 7 Key for Relays, or
Press 8 Key for SLC Outputs, or
Press 9 Key for RRM Group
6a
Press 1 Key for Relay 1, or
Press 2 Key for Relay 2, or
Press 3 Key for Relay 3, or
Press 4 Key for Trouble Relay
(if Relays selected in Step 6)
7
Press 1 Key and then press "Enter" Key
8
Return to Step 6 and make another selection
(optional)
9
De-activate all outputs after confirming proper
operation
10
Press "Backspace" Key (as required)
August 2013
Purpose: To manually activate control-unit outputs during system
testing to confirm proper operation.
Action
3-88
Result
Initiate Menu Access
Gain access to menus
Enter Test-Menu branch
Access additional Test-Menu options
Select "Output Test" option
Specify output to activate
Specify relay to activate
Initiate output activation specified in Step 6 and
6a
Activate additional outputs
See Paragraph 3-2.5.2.5.11
Exit Menu System
P/N 06-236530-001