3-2.5.2.4.34 How to Clear the Contents of the SLC-Initiating Devices Test Log
Step
1
Press 0 Key
2
Enter Password; press "Enter" Key
3
Press 3 Key
4
Press "Scroll" Key
5
Press 4 Key
6
Press "Scroll" Key twice
7
Press 8 Key
8
Press 1 Key
9
Enter starting SLC address and ending SLC
address.
Use XXX format for addresses.
Press "Enter" Key to confirm address range to
clear.
10
Press "Backspace" Key (as required)
3-2.5.2.4.35 How to Clear the Contents of the Walk-Test Log
Step
1
Press 0 Key
2
Enter Password; press "Enter" Key
3
Press 3 Key
4
Press "Scroll" Key
5
Press 4 Key
6
Press "Scroll" Key twice
7
Press 8 Key
8
Press 2 Key
9
Enter starting SLC address and ending SLC
address.
Use XXX format for addresses.
Press "Enter" Key to confirm address range to
clear.
10
Press "Backspace" Key (as required)
August 2013
Purpose: To remove the most-recently recorded results of initiating
devices tests from the SLC Test Log. All initiating devices are tested
once per day to confirm that they can transmit an acceptable event-
detection signal. The results of the most-recently-transmitted event
signal are recorded in the SLC Test Log.
Action
Purpose: To remove the most-recently recorded results of initiating-
devices walk tests from the Walk-Test Log. The results of the most-
recently-conducted walk tests are recorded in the Walk-Test Log.
Action
3-58
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access additional Set-Menu options
Select Programming option
Access additional Programming-Menu options
Select "Clear Tests" option
Select "Clear SLC Tests"
Specify range of SLC initiating devices to have
test results cleared
Exit Menu System
Result
Initiate Menu Access
Gain access to menus
Enter Set-Menu branch
Access additional Set-Menu options
Select "Programming" option
Access additional Programming-Menu options
Select "Clear Tests" option
Select "Clear Walk Tests"
Specify range of SLC initiating devices to have
walk-test results cleared
Exit Menu System