Kidde ARIES Installation, Operation And Maintenance Manual page 195

Fire alarm/suppression
Table of Contents

Advertisement

Device Address 010
Figure 3-27. Typical Display after Acknowledgment of Release Message
P/N 06-236530-001
The display will show the following message when an extinguishing
system has been released:
Release Circuit
AR2
SYSTEM RELEASE
POWER ROOM
Zone-Specific
Custom Message
Figure 3-26. Typical Release Message
Press the <ACKNOWLEDGE> Key when the message in Figure 3-26
appears to silence the buzzer. The display will change as shown in
Figure 3-27. You may then manually scroll the display using the
<SCROLL> Key to show any other suppression zones (successively
by order of occurrence, if applicable) that have begun to count down
after the release in the first suppression zone. Otherwise, you may
manually scroll the display to show the completed Level-1 events and
active Level-2 events which will appear as shown in Figure 3-29.
Alarm Indication
010 ALARM ON PHOTOELECTRIC (SCROLLTOVIEW)
DIS 01
CNTDN 00
No. of Extinguishing-System Releases
A new event will not automatically override the appearance of the
display when a countdown to release is in progress. The appropriate
LED on the display will flash and the buzzer will sound when any new
system event is reported, and the new event will be logged. The new
event will only be displayed when the <ACKNOWLEDGE> Key is
pressed.
Release Message
Device Type Reporting Alarm
ABT 00 ALM 02
PAS 00
No. of Alarms
No. of Activated Abort Stations
No. of Countdowns to Release in Progress
3-113
No. of PAS
Countdowns in Progress
August 2013