Kidde ARIES Installation, Operation And Maintenance Manual page 203

Fire alarm/suppression
Table of Contents

Advertisement

Device Address 205
P/N 06-236530-001
Trouble Not-Registered Indication
205 NOT REGISTERED ON UNKNOWN TYPE
UNUSED SLC DEVICE
Figure 3-48. Typical Device Not Registered Message
4. Wait for all of the device-not-registered troubles to report. Press the
<ACKNOWLEDGE> Key one or more times to silence the control unit buzzer.
5. Confirm that no more trouble messages have been reported.
6. Record the number of currently-active troubles. The number of troubles
should be equal to the number of SmartOne devices connected to the SLC.
7. Run the AutoLearn Routine as follows:
a. Press the 0 Key. This display will show this message:
PLEASE ENTER PASSWORD
* * * * * *
Figure 3-49. Password Prompt
b. Press the default Level-2 Password keys (186591) and then press the
<Enter> Key. The top-level menu selections will be displayed:
1: ISOLATE
3: SET
Figure 3-50. Top-Level Menu Selections
c. Press the 3 Key to select "SET"
1: TIME/DATE
3: SLC DEVICES
Figure 3-51. Set Menu
d. Press
the
"PROGRAMMING"
4: PROGRAMMING
6: NETWORK (FUTURE)
Figure 3-52. Additional Set-Menu Selections
e. Press 3 to select "AUTOLEARN"
1: DAY/NIGHT
3: AUTOLEARN
Figure 3-53. Programming Sub-Menu
Figure 3-54 shows a typical message that displays when the AutoLearn
routine is running.
Device Type Not Known
at This Time
2: LIST
4: TEST
2: PORT CONTROL
SCROLL FOR MORE
<SCROLL>
Key
and
5: GLOBALS
SCROLL FOR MORE
2: PASSWORDS
SCROLL FOR MORE
3-121
then
the
4
Key
August 2013
to
select