P/N 06-236530-001
6. Press the <Scroll> Key twice and then press the 9 Key to select RESYNCH
NETWORK.
7: CLEAR EVENTS
8: RESYNCH NETWORK
Figure 3-92. Resynch Network Option
7. Press the 1 Key when no groups are used or press the 2 Key when
groups are being used, then press the <ENTER> Key when prompted
by the message below.
Figure 3-93. Resynch Network Display
8. Enter the network group number as indicated below when groups are
being used:
Figure 3-94. Network Group Prompt
9. Press the <Backspace> Key multiple times as required to exit from
the Menu State.
The events being displayed on the control unit will now be consistent with
the events being displayed on all of the networked control units.
3-143
*
August 2013