Kidde ARIES Installation, Operation And Maintenance Manual page 6

Fire alarm/suppression
Table of Contents

Advertisement

another level or floor of a building. A second floor detector, for example, may not sense a first floor or
basement fire.
Furthermore, all types of smoke detectors, both ionization and photoelectric types, have sensing limitations. No
type of smoke detector can sense every kind of fire caused by carelessness and safety hazards such as smoking
in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits,
children playing with matches, or arson.
Notification appliances, such as bells, may not alert people if these appliances are located on the other side
of closed or partly open doors or are located on another floor of a building.
A fire alarm system will not operate without electrical power. If AC power fails, the system will operate from
standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-
rise feature of each detector should be tested by a qualified fire protection specialist as recommended in
NFPA 72, Chapter 10.
Auxiliary Equipment used in the system may not be technically compatible with the control unit. It is
essential to use only equipment listed for service with your control unit.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be
out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and
system wiring should be tested and maintained by professional fire alarm installers following written
procedures supplied with each device. System inspection and testing should be scheduled monthly or as
required by national and/or local fire codes. Adequate written records of all inspections should be kept.
GENERAL SAFETY NOTICES
The following general safety notices supplement specific warnings and cautions appearing in the manual.
The safety precautions in this section must be understood and applied during operation and maintenance.
This manual is to be used by trained distributors/technicians. The entire manual should be read and fully
understood prior to installation.
FIRST AID
Any injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention
immediately.
GENERAL PRECAUTIONS
The following general safety precautions are to be observed at all times:
1.
All electrical components associated with equipment shall be installed and grounded in accordance
with NEC and local regulatory requirements.
2.
Special precautionary measures are essential to prevent applying power to equipment at any time
maintenance work is in progress.
3.
Before working on electrical equipment, use a voltmeter to ensure that system is not energized.
4.
When working near electricity, do not use metal rulers, flashlights, metallic pencils, or any other ob-
jects having exposed conductive material.
5.
When connecting a meter to terminals for measurement, use a voltage range higher than expected
voltage to be measured.
August 2013
SAFETY SUMMARY (CONT.)
The following must be observed to maintain personnel safety.
iv
P/N 06-236530-001

Advertisement

Table of Contents
loading

Table of Contents