3-2.5.2.2.2
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 1 Key
4
Press 1 Key
5
Press 1 Key for SLC inputs or 2 Key for SLC
outputs.
Press "Enter" Key to confirm selection.
6
Use keypad to enter single device or range of
devices to isolate.
Press "Enter" Key to confirm selection.
7
Press 2 Key and then press "Enter" Key to confirm
selection.
Press "Backspace" Key (as required)
3-2.5.2.2.3
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 1 Key
4
Press 2 Key
5
Press 1 Key for NACs or
Press 2 Key for Release Circuits or
Press 3 Key for Combo Circuits
Press 4 Key for Relays
6
Use keypad to enter single output or range of
outputs to isolate.
Press "Enter" Key to confirm selection.
7
Press 1 Key and then press "Enter" Key to confirm
selection
8
Press "Backspace" Key (as required)
9
Press "Acknowledge" Key
August 2013
How to De-Isolate SLC Devices
Purpose: To enable the ARIES Control Unit to process initiating and
trouble signals from previously-isolated SmartOne automatic detectors
and monitor modules. Also to enable previously-isolated SmartOne
control and relay modules to execute activation instructions issued by
the ARIES Control Unit.
Action
How to Isolate Control-Unit-Based Outputs
Purpose: To prevent selected control-unit-based outputs from carrying
out activation instructions issued by the ARIES Control Unit.
Action
3-14
Result
Initiate menu access
Gain access to menus
Enter Isolate-Menu branch
Select "SLC Devices" option
Select "SLC Inputs" or "SLC Outputs."
Get prompt to Isolate or De-Isolate
Execute De-Isolation Routine for single device or
range of devices entered in Step 6.
Exit Menu System
Result
Initiate menu access
Gain access to menus
Enter Isolate-Menu branch
Select "Outputs" option
Select output to isolate
Get prompt to Isolate or De-Isolate
Execute Isolation Routine for single output or
range of outputs entered in Step 6.
Exit Menu System
Silence buzzer and change Supervisory LED from
flashing to steady.