Kidde ARIES Installation, Operation And Maintenance Manual page 97

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.2.4
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 1 Key
4
Press 2 Key
45
Press 1 Key for NACs or
Press 2 Key for Release Circuits or
Press 3 Key for Combo Circuits
Press 4 Key for Relays
6
Use keypad to enter single output or range of
outputs to de-isolate.
Press "Enter" Key to confirm selection.
7
Press 2 Key and then press "Enter" Key to confirm
selection
8
Press "Backspace" Key (as required)
3-2.5.2.2.5
Step
1
Press 0 Key
2
Enter Password
3
Press 1 Key
4
Press "Scroll" Key
5
Press 7 Key
6
Use keypad to enter single HSSD or range of
HSSDs to isolate.
Press "Enter" Key to confirm selection
7
Press 1 Key and then press "Enter" Key to confirm
selection.
8
Press "Acknowledge" Key
9
Press "Backspace" Key (as required)
P/N 06-236530-001
How to De-Isolate Control-Unit-Based Outputs
Purpose: To enable previously-isolated control-unit-based outputs to
execute activation instructions issued by the ARIES Control Unit.
Action
How to Isolate High-Sensitivity Smoke Detectors (HSSDs)
Purpose: To prevent initiating and trouble signals from selected HSSDs
connected to an IIM from being processed and acted upon by the
ARIES Control Unit.
Action
3-15
Result
Initiate menu access
Gain access to menus
Enter Isolate-Menu branch
Select "Outputs" option
Select output to de-isolate
Get prompt to Isolate or De-Isolate
Execute De-Isolation Routine for single output or
range of outputs entered in Step 6.
Exit Menu System
Result
Initiate menu access
Gain access to menus
Enter Isolate-Menu branch
Access additional options
Select "HSDs" option
Get prompt to Isolate or De-Isolate
Execute Isolation Routine for single HSSD or
range of HSSDs entered in Step 6.
Silence buzzer and change Supervisory LED from
flashing to steady
Exit Menu System
August 2013